欢迎来天津英联石油设备技术服务有限公司官网!
天津英联石油设备技术服务有限公司
022-25711889
服务咨询热线
Tianjin Yinglian Petroleum Equipment Technology Service Co., Ltd.
产品展示
当前位置:
ProSafe-RS
    发布时间: 2021-09-16 10:28    
ProSafe-RS





GENERAL


This GS describes the hardware specifications of the analog I/O modules that can be mounted on the safety node


unit (SNB10D) and the safety control unit (SSC10 or SSC50).


STANDARD SPECIFICATIONS


Current Input Module


This module inputs 4 to 20 mA signals from the field.


The SAI143 can be made dual redundant.



*1: No Zener barriers can be connected to this module. An isolation barrier should be used when an intrinsic safety instrument-

ed system is used.

*2:  500 V AC when dedicated signal cable is used.




Voltage Input Module


This module inputs 1 to 5 V/1 to 10 V signals from the field.


The SAV144 can be made dual redundant.



*1:  500 V AC when dedicated signal cable is used.




Current Output Module


This module outputs 4 to 20 mA signals to the field.


The SAI533 can be made dual redundant.






GENERAL


This GS provides the hardware specifications of the digital I/O modules that can be installed in the Safety Node Unit


(SNB10D) and Safety Control Units (SSC10 and SSC50).


STANDARD SPECIFICATIONS


Input Module


Input modules accept a contact signal from the field. SDV144 can be made dual-redundant.




If SDV144 field wiring diagnostic functions are used, the following diagnostic elements should be installed for individu-


al channels in the vicinity of the field equipment:


• SCB100 (for defective open circuit detection while accepting off signals) (*1)


• SCB110 (for defective short-circuit detection while accepting on signals) (*2)


*1:  Input signals are normally off while in normal operation.


*2:  Input signals are normally on while in normal operation.




下一个: