No. of serial ports |
4 |
Protocol |
RS232, RS422, RS485 |
Baud rate, AutroSafe Specification |
9600 baud |
Communication parameters in AutroSafe application |
8 data, 1 stop bit and no parity |
Short circuit protection |
All outputs protected against continuous short circuit |
RS-232 mode Input impedance: Input voltage swing: Output voltage swing |
3KΩ min ±30V max ± 5V min, ± 7V typical |
RS-422. RS-485 modes Differential input threshold: Input impedance: Input current: Differential output voltage: High/low states differential output voltage symmetriy: |
-0,2V min, +0,2V max 12KΩ min 2,0V min (RL = 50Ω) 0,2V max |
I/O header (plugs) or screw terminals |
Two 20-position (2x10). 025″ square pin header on .1″centres. Headers mate with standard ribbon cable (IDC) connectors. (Two 20-position terminal blocks X1 and X2 |
Power Supply |
+5VDC ± 10 |
Current Consumption |
80mA typical, all outputs unloaded |
Operating Temperature |
-40° to +85°C standard |
PC/104 bus |
8 bit and 16 bit bus headers are installed and used (16-bit header is used for interrupt levels only) |